DocumentCode
1106229
Title
The Oxide Film Lightning Arrester
Author
Steinmetz, Charles P.
Issue
2
fYear
1918
fDate
7/1/1918 12:00:00 AM
Firstpage
871
Lastpage
880
Abstract
A short history of lightning protection of electric systems is given, as relating to the three successive types of electric circuits; the communication circuits, the power circuits of negligible electrostatic capacity, and the high-power circuits containing distributed capacity and inductance and capable of electric oscillation, leading to the three problems of discharging over-voltage to ground, opening the power current which follows the discharge and discharging so that no power current follows even for a fraction of a half wave. It is shown that these problems are solved by the spark gap to ground, by the use of non-arcing metals in the multigap arrester, which opens the circuit at the end of a half wave of current, and by the so-called ``counter e.m.f.´´ type of arrester, represented by the aluminum cell and the oxide film arrester. It is shown that the necessity of taking care of recurrent discharges in high-power systems had led to the universal adoption of the aluminum cell arrester in such systems, in spite of its disadvantage of requiring daily attendance in charging, and of containing an electrolyte and oil. In the oxide film arrester a type of arrester is presented which has the same characteristics and therefore the same advantages as the aluminum cell arrester, but does not require daily attendance and contains no liquids.
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1918.4765563
Filename
4765563
Link To Document