DocumentCode :
1107656
Title :
Assessment of insulation condition in rotating machine stators
Author :
Gupta, B.K. ; Culbert, I.M.
Author_Institution :
Ontario Hydro, Toronto, Ont., Canada
Volume :
7
Issue :
3
fYear :
1992
fDate :
9/1/1992 12:00:00 AM
Firstpage :
500
Lastpage :
508
Abstract :
The authors describe an attempt to assess the condition of stator insulation in standby generators in two generating stations. The insulation condition was estimated by comparing diagnostic test results for different machines with similar insulator or for different phases of the same machine. The diagnostic tests included measurements of insulation resistance, partial discharges, and capacitance and dissipation factors as well as AC and DC hipot tests. The methods used to assess the insulation system are outlined in detail, and the assessment results are described and discussed
Keywords :
electric breakdown of solids; insulation testing; machine insulation; partial discharges; standby generators; stators; capacitance; diagnostic test; dissipation factors; hipot tests; insulation testing; machine insulation; measurements; partial discharges; standby generators; stators; Coils; Electric breakdown; Electric variables measurement; Insulation testing; Machinery; Manufacturing; Power measurement; Rotating machines; Standby generators; Stators;