DocumentCode
1107810
Title
Radio Frequency Response of a Large Turbine-Generator Stator Winding
Author
Emery, F.T. ; Harrold, R.T.
Author_Institution
Westinghouse Electric Corporation, Steam Turbine Generator Division, Orlando, Florida 32817
Issue
2
fYear
1986
fDate
6/1/1986 12:00:00 AM
Firstpage
172
Lastpage
179
Abstract
Long term experience with on-line radio frequency monitoring of large turbine generators has shown a need for increased understanding of the propagation of arc generated radio frequency signals in a stator winding. This paper presents the results of an on going research program designed to obtain an increased understanding of radio frequency arc detection in large turbine generators. Test results from AC arcing response and sinewave response measurements made on a generator stator are presented in addition to the results obtained from a computer circuit analysis performed on a radio frequency circuit model of a portion of the same generator stator. These results led to a better understanding of RF arc signal propagation and helped to identify improved detection techniques. Three RF measurement techniques were studied for both the measurements and calculations, resulting in good agreement. Arc voltage detection sensitivity calculations give a minimum detectable level of arc voltage for each RF measurement technique.
Keywords
AC generators; Circuit analysis computing; Circuit testing; Measurement techniques; RF signals; Radio frequency; Signal generators; Stator windings; Turbines; Voltage;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.1986.4765717
Filename
4765717
Link To Document