• DocumentCode
    1108330
  • Title

    Sizing Batteries for Generating Stations

  • Author

    Migliaro, M.W.

  • Author_Institution
    EBASCO SERVICES INCORPORATED, NEW YORK, NY
  • Issue
    4
  • fYear
    1986
  • Firstpage
    25
  • Lastpage
    30
  • Abstract
    Sizing of storage batteries is straight forward using the formulas in IEEE 485; however the key to proper sizing is the determination of the duty cycle. This paper will discuss voltage considerations, loads and the duty cycle, as they relate to battery sizing. Illustrative examples are provided as required. Although the emphasis of this paper will be on batteries for generating station stationary applications, uninterruptible power supply (UPS) system batteries are also discussed. A UPS system is a constant kVA load and battery sizing, using the kW method discussed, is preferable in this case. The guidance provided will enable the user to determine the requirements for a specific application and properly size the battery. Although this paper discusses generating stations, the material presented is applicable to other installations, including substations, industrial control and communications systems.
  • Keywords
    Batteries; Chemicals; Frequency; Gravity; Industrial control; Power generation; Testing; Uninterruptible power systems; Ventilation; Voltage;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/TEC.1986.4765769
  • Filename
    4765769