DocumentCode
1108674
Title
Adjustable-speed drive retrofit for Ormond Beach FD fans
Author
Oliver, J.A. ; Weiss, H.W. ; McCluskey, R.K. ; Samotyj, M.J.
Author_Institution
Bechtel Corp., Norwalk, CA, USA
Volume
7
Issue
3
fYear
1992
fDate
9/1/1992 12:00:00 AM
Firstpage
580
Lastpage
588
Abstract
The boiler on Southern California Edison´s 750 MW Ormond Beach Unit 2 was extensively modified to reduce minimum load from 250 MW to 36 MW. With the unit operating at minimum load frequently at night, it became economically attractive to install adjustable speed drives (ASDs) on each of the 6250 hp forced draft fan motors. The authors describe the application concept that has evolved from the EPRI tests, the specific development features in the new ASDs field test results of power savings, measured harmonics at the utility bus and at the motor, the effect of THD reduction by using an input harmonic filter, and operating experience. Fan inlet vanes have been removed, and no ASD bypass was provided
Keywords
boilers; commissioning; maintenance engineering; project engineering; thermal power stations; variable speed drives; 250 MW; 36 MW; 6250 hp; 750 MW; USA; adjustable speed drives; boiler; development; filter; forced draft fan motors; harmonics; load; maintenance; project engineering; retrofitting; testing; thermal power stations; Blades; Boilers; Fans; Harmonic filters; Power generation economics; Power harmonic filters; Power measurement; Power system harmonics; Testing; Variable speed drives;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.148581
Filename
148581
Link To Document