DocumentCode
1108951
Title
Fault analysis and special tests of thyristor for RFX AC/DC converters
Author
Gaio, E. ; Piovan, R. ; Maschio, A. ; Tenconi, S.
Author_Institution
Istituto Gas Ionizzati, Padova, Italy
Volume
5
Issue
1
fYear
1990
fDate
1/1/1990 12:00:00 AM
Firstpage
372
Lastpage
378
Abstract
In the RFX nuclear fusion experiment, 20 AC/DC converter units, for a total installed power of over 400 MVA, are used to feed the machine magnets. Due to the special characteristics of the load, and in particular to the expected fault conditions, the converter bridges must withstand a high number (approximately 2000) of severe overloads during the life of the machine; in particular, the thyristors must carry a current two or three times larger than the nominal current without any damage. In addition, the thyristors must not explode, even in the case of a slightly higher surge current than the previous one, when the fuse does not blow quickly. As the manufacturer´s data did not cover the thyristor performance under these specific requirements, new tests on the thyristors had to be carried out, and the results are discussed
Keywords
failure analysis; power convertors; surges; testing; thyristor applications; 400 MVA; AC/DC converters; RFX nuclear fusion experiment; fault conditions; machine magnets; overloads; surge current; tests; thyristors; Bridges; DC-DC power converters; Feeds; Fuses; Fusion reactors; Magnetic analysis; Magnets; Surges; Testing; Thyristors;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.107300
Filename
107300
Link To Document