Title :
A Study of the Frequency Response of Turbogenerators with Special Reference to Nanticoke G. S.
Author :
Jack, A.G. ; Bedford, T.J.
Author_Institution :
University of Newcastle upon Tyne
Abstract :
The results from the standstill frequency response tests on three selected turbogenerators are critically examined. Particular attention is paid to the Nanticoke machine. A reason for the large difference between this machine´s performance as predicted using data derived from standstill tests as compared to that predicted using data from on-line tests is proposed. Use is made of the finite element method linked to simple external circuits.
Keywords :
Circuit testing; Conductors; Finite element methods; Frequency response; Lifting equipment; Predictive models; Skin; System testing; Turbogenerators; Voltage;
Journal_Title :
Energy Conversion, IEEE Transactions on
DOI :