DocumentCode
1109582
Title
Application of an On-Line Air Gap Monitor for Hydroelectric Generator Protection and Problem Diagnosis
Author
Talas, P. ; Franklin, D.E. ; Toom, P.O. ; Palylyk, R.A.
Author_Institution
B.C. Hydro and Power Authority, Vancouver, British Columbia, CANADA
Issue
4
fYear
1987
Firstpage
526
Lastpage
533
Abstract
This paper presents the application of a new hydroelectric generator air gap measurement system. It is a continuous on-line system using optical triangulation, fiber-optics, a microprocessor-based monitor, specially developed instrumentation and power supplies. This system is non-invasive, insensitive to EMI and has 0.2% accuracy over a range of 2 to 40 mm. The paper presents air gap data obtained from B.C. Hydro´s Mica Creek Unit G2 (457 MVA) during March 1986. Readings were taken from stator-to-rotor and from rotor-to-stator to determine the unit´s characteristics prior to rotor rim shrink modifications. This data assisted in determining the individual contributions of the rotor and the stator to the generator´s behavior and provides a comparison for post-modification testing.
Keywords
Electromagnetic interference; Hydroelectric power generation; Instruments; Monitoring; Optical fibers; Power supplies; Power system protection; Rotors; Stators; Testing;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.1987.4765888
Filename
4765888
Link To Document