    Turn Insulation Capability of Large AC Motors Part 3 - Insulation Coordination

  • Author

    Gupta, B.K. ; Lloyd, B.A. ; Stone, G.C. ; Sharma, D.K. ; Nilsson, N.E. ; Fitzgerald, J.P.

  • Author_Institution
    Ontario Hydro, Research Division, Toronto, Ontario, CANADA
  • Issue
    4
  • fYear
    1987
  • Firstpage
    674
  • Lastpage
    679
  • Abstract
    The coordination of the surge strength of large AC motor stator windings with the surge voltages encountered during normal switching of the motors in utility generating stations is described in this paper. The surge strength of the turn insulation of motor windings was determined from destructive tests on 17 stators [6]. The surge voltage magnitude which can strike the motor´s terminals was measured on 33 motors during normal operation in several different utility generating stations [5]. The surge strength of most motors exceeds the surge magnitudes which can occur during normal service. The only motors which have a surge strength below the highest surge voltages measured were either damaged from severe aging, or had poorly made turn insulation when compared to other coils in the same stator. Vacuum switchgear does not appear to pose a greater hazard to motor windings than conventional air-magnetic breakers, as long as the vacuum circuit breaker does not interrupt motor starting currents. Improved quality control tests are required to allow manufacturers to identify the few defective coils which may occur in a winding.
  • Keywords
    AC generators; AC motors; Aging; Coils; Hazards; Insulation testing; Stator windings; Surges; Switchgear; Voltage;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/TEC.1987.4765908
  • Filename
    4765908