Title :
Suppression of Ground-Fault Arcs on Single-Pole-Switched EHV Lines by Shunt Reactors
Author_Institution :
Bonneville Power Administration, Portland, Oreg.
fDate :
3/1/1964 12:00:00 AM
Abstract :
Arcing line-to-ground faults isolated by single-pole switching are maintained by capacitive coupling between the faulted and unfaulted phases. Such faults are difficult to extinguish on long EHV (extra-high-voltage) lines because the fault A promising remedy consists of neutralizing the capacitive coupling by shunt reactors, which are required anyhow on many lines for compensating the normal charging current.
Keywords :
Capacitance; Circuit faults; Conductors; Coupling circuits; Inductors; Power system faults; Shunt (electrical); Switching circuits; Voltage; Wires;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :