Title :
Parallel Operation of AC and DC Power Transmission
Author :
Peterson, H.A. ; Reitan, D.K. ; Phadke, A.G.
Author_Institution :
College of Engineering, the University of Wisconsin, Madison, Wis.
Abstract :
A preliminary account has already been given of the EHV composite ac-dc study initiated last year at the University of Wisconsin [1]. This paper presents additional results obtained in the study of parallel EHV ac-dc power transmission in a basic 2-machine equivalent system. The consequences of 3-phase faults on inverter commutation are evaluated, and circumstances leading to inverter commutation failure (shoot-through) are made clear for various conditions of initial loadings and faulting. The consequences of inverter shoot-through onsystem stability are also evaluated for the 2-machine case. The characteristics of the control arrangement for a dc line are expected to be of special significance in determining the final overall performance of composite ac-dc systems.
Keywords :
Commutation; Control systems; Erbium; Interconnected systems; Inverters; Load flow; Power transmission; Rectifiers; Stability; Voltage control;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1965.4766103