• DocumentCode
    1112598
  • Title

    Power Line Carrier Coupling Investigations on a 500-kV Line

  • Author

    Bozoki, B. ; Jones, D.E.

  • Author_Institution
    The Hydro-Electric Power Commission of Ontario, Toronto, Ont., Canada.
  • Volume
    84
  • Issue
    3
  • fYear
    1965
  • fDate
    3/1/1965 12:00:00 AM
  • Firstpage
    197
  • Lastpage
    200
  • Abstract
    Some previously accepted concepts of power line carrier coupling do not apply on power lines with very few transpositions. For such lines, the attenuation and impedance of the carrier circuit may be strongly dependent on which phase conductor is selected for coupling. This phenomenon has been investigated in a series of tests on a long 500-kV line with one transposition near the middle. The results, which are explained in terms of the modal propagation theory, show a difference of as much as 15 dB in attenuation at certain frequencies between the optimum and a more conventional form of carrier coupling.
  • Keywords
    Attenuation; Circuit testing; Conductors; Coupling circuits; Earth; Frequency; Impedance; Phase measurement; Signal analysis; Velocity measurement;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1965.4766175
  • Filename
    4766175