Title :
Harmonic Composition of Low-Frequency Electromagnetic Emissions Associated with High-Voltage Transmission
Author :
Daley, Michael L. ; Benitez, Henry ; Zajac, Herbert ; Chartier, Vernon
Author_Institution :
Engineering Laboratory, Division of Neurosurgery, Oregon Health Sciences University, Portland, OR 97201
Abstract :
Electric-field-strength measures of the spectrum between 10 and 200 kHz were obtained under dry conditions near a 500-kV transmission line. Comparison of the magnitudes of electric field strength between the odd and even harmonics of 60 Hz revealed a marked asymmetry. The ratio of odd to even harmonic field strength ranged from 19 to 3.3. A primary source of these emissions may be produced by components within the power systems with nonlinearities that are best described by odd functions.
Keywords :
Access protocols; Algorithms; Assembly; High level languages; Memory; Operating systems; PROM; Registers; Runtime library; 500-kV transmission line; Undesired emission; harmonics;
Journal_Title :
Electromagnetic Compatibility, IEEE Transactions on
DOI :
10.1109/TEMC.1985.304295