  • Abstract
    For nearly 28000 transients, appearing at 40 measuring places during a total measuring time of about 3400 h on low-voltage supply networks in industrial and nonindustrial areas, time-domain parameters were determined. Of about one-third of the transient disturbances, a Fourier transform yielded frequency-domain data. After a description of the automated measuring system (AMS), results of measurements are presented. A statistical evaluation of several time-and frequency-domain transient parameters proved to be possible. In additional analyses, parameters are derived which are of interest in electro-magnetic-disturbance calculations and conducted-susceptibility tests.
  • Keywords
    Area measurement; Electromagnetic analysis; Electromagnetic measurements; Electromagnetic transients; Frequency domain analysis; Switches; Testing; Time domain analysis; Time measurement; Voltage; Transient disturbances; frequency domain; low-voltage power lines; measured data; statistical evaluation; time-domain;