Abstract :
This paper gives the results to date of radio influence and corona loss tests performed at a voltage of 775 kV at the extra-high-voltage test project at Apple Grove, W. Va., a joint research project sponsored by the American Electric Power Service Corporation and Westinghouse Electric Corporation with six other participating companies. Effects of line radio-influence terminations and larger centerphase conductors are discussed. Radio influence and corona loss results are given for there test lines utilizing 4-conductor bundles with subconductor diameters of 1.0, 1.196, and 1.382 inches.
Keywords :
Aluminum; Conductors; Corona; Dielectrics and electrical insulation; Hardware; Performance evaluation; Poles and towers; Steel; Testing; Voltage;