DocumentCode
1113162
Title
A New Method of Analysis for Multigrounded Cable Shields Inductively And Conductively Coupled to Multigrounded-Neutral Power Lines
Author
Levey, Lawrence
Author_Institution
Bell Communications Research, Inc., Morristown, NJ 07960
Issue
2
fYear
1987
fDate
5/1/1987 12:00:00 AM
Firstpage
116
Lastpage
125
Abstract
A configuration in which a communications cable with a multigrounded shield has a length that is inductively and conductively coupled to a multigrounded-neutral conductor of a power line is analyzed. A new formulation is given for the power-frequency voltages and currents that develop along the shield and core of the cable. A simplified network is derived for the coupled systems from which the variables of the formulation can be evaluated. There are no restrictionson the uniformity of the grounds, the spacing of bonds, or the terminations. The procedures aredirectly applicable to the evaluation of shielding effectiveness and to protection problems arising from power faults.
Keywords
Cable shielding; Circuits; Communication cables; Conductors; Earth; Impedance; Power cables; Power system modeling; Power system protection; Voltage; Cable coupling; coupling model; grounding; power line; shielded communications cable;
fLanguage
English
Journal_Title
Electromagnetic Compatibility, IEEE Transactions on
Publisher
ieee
ISSN
0018-9375
Type
jour
DOI
10.1109/TEMC.1987.304350
Filename
4091868
Link To Document