• DocumentCode
    1115917
  • Title

    Development and testing of power assisted current limiting fuses to 600 amperes and 38 kV

  • Author

    Pflanz, H.M. ; Acree, J.A. ; Schaffer, J.S.

  • Author_Institution
    G&W Electric Co., Blue Island, IL, USA
  • Volume
    3
  • Issue
    2
  • fYear
    1988
  • fDate
    4/1/1988 12:00:00 AM
  • Firstpage
    619
  • Lastpage
    626
  • Abstract
    The design and testing of a multielement current limiting fuse with ratings of 200 to 600 A continuous current, 2.4 to 38 kV, and fault currents to 25 kA (RMS, sym) are discussed. The device is power assisted; however, it does not utilize an auxiliary electronic triggering means. Operation is triggered by voltage drop or by melting of an element carrying load current. The device can provide effective fault protection at a variety of current levels not previously accommodated. Applications include the paralleling of current-limiting reactors and the protection of underrated systems resulting from cogeneration of source improvements
  • Keywords
    electric fuses; testing; 2.4 to 38 kV; 200 to 600 A; 25 kA; current-limiting reactors; load carrying element melting; power assisted current limiting fuses; testing; voltage drop; Bridge circuits; Circuit faults; Conductors; Current limiters; Fault currents; Fuses; Inductors; Power system protection; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.4300
  • Filename
    4300