Title :
Power HV circuit breakers with severe capacitive switching duty
Author :
Canelhas, A. ; Bengtsson, B. Å ; Margaard, T. ; Strandem, A. ; Alvinsson, R.
Author_Institution :
ABB Power Syst., Sweden
Volume :
9
Issue :
2
fYear :
1994
fDate :
4/1/1994 12:00:00 AM
Firstpage :
842
Lastpage :
848
Abstract :
It has often been found necessary to operate HVDC converter station circuit breakers to disconnect a major capacitive load from the main AC buses under severe transient overvoltage conditions. This paper describes results of tests made on a conventional puffer breaker aimed at gaining knowledge of the consequences of a restrike on the breaker itself. The paper also proposes a method to reduce the transient recovery voltage (TRV) requirements imposed on power circuit breakers in order to be able, in most of the cases, to use standard devices for capacitive breaking. The method is based on application of metal-oxide resistors in parallel with the breaker contacts. The phenomena described in this paper are in all aspects valid for any power system which can have the cases presented
Keywords :
DC power transmission; gas blast circuit breakers; overvoltage; power capacitors; power convertors; resistors; restriking voltage; HVDC converter station; capacitive load disconnection; capacitive switching duty; metal-oxide resistors; power HV circuit breakers; puffer breaker; restrike; transient overvoltage; transient recovery voltage; Circuit breakers; Circuit faults; HVDC transmission; Power system harmonics; Power system transients; Resistors; Surges; Switching circuits; Transient analysis; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.296265