• DocumentCode
    1116759
  • Title

    Behavior of post arc gas after arc interruption on UHV (1000 kV class) transmission lines

  • Author

    Goda, Yutaka ; Matsuda, Shoji ; Inaba, Tsuginori ; Ozaki, Yuzo

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Kanagawa, Japan
  • Volume
    9
  • Issue
    2
  • fYear
    1994
  • fDate
    4/1/1994 12:00:00 AM
  • Firstpage
    887
  • Lastpage
    893
  • Abstract
    It is very important to know the insulation recovery time after arc interruption for selecting the adequate reclosing dead time of rapid auto-reclosing on transmission lines. In order to study insulation recovery characteristics after arc interruption on UHV (1000 kV class) transmission lines, many tests were carried out. Full size insulator assemblies were used for measurements of insulation recovery characteristics after arc interruption, and the behavior of post arc gases, which strongly influence the insulation recovery characteristics, was investigated. In this paper the authors describe the behavior of post arc gases after arc interruption of UHV transmission lines
  • Keywords
    circuit-breaking arcs; high-voltage engineering; insulation testing; power transmission lines; 1000 kV; UHV transmission lines; arc interruption; buoyancy height; insulator assemblies; post arc gas behaviour; rapid auto-reclosing; reclosing dead time; Assembly; Gas insulation; Gases; Insulation testing; Insulator testing; Poles and towers; Power transmission lines; Size measurement; Transmission line measurements; Transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.296271
  • Filename
    296271