DocumentCode
1116759
Title
Behavior of post arc gas after arc interruption on UHV (1000 kV class) transmission lines
Author
Goda, Yutaka ; Matsuda, Shoji ; Inaba, Tsuginori ; Ozaki, Yuzo
Author_Institution
Central Res. Inst. of Electr. Power Ind., Kanagawa, Japan
Volume
9
Issue
2
fYear
1994
fDate
4/1/1994 12:00:00 AM
Firstpage
887
Lastpage
893
Abstract
It is very important to know the insulation recovery time after arc interruption for selecting the adequate reclosing dead time of rapid auto-reclosing on transmission lines. In order to study insulation recovery characteristics after arc interruption on UHV (1000 kV class) transmission lines, many tests were carried out. Full size insulator assemblies were used for measurements of insulation recovery characteristics after arc interruption, and the behavior of post arc gases, which strongly influence the insulation recovery characteristics, was investigated. In this paper the authors describe the behavior of post arc gases after arc interruption of UHV transmission lines
Keywords
circuit-breaking arcs; high-voltage engineering; insulation testing; power transmission lines; 1000 kV; UHV transmission lines; arc interruption; buoyancy height; insulator assemblies; post arc gas behaviour; rapid auto-reclosing; reclosing dead time; Assembly; Gas insulation; Gases; Insulation testing; Insulator testing; Poles and towers; Power transmission lines; Size measurement; Transmission line measurements; Transmission lines;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.296271