DocumentCode
1117041
Title
Analysis of DC arc furnace operation and flicker caused by 187 Hz voltage distortion
Author
Tang, L. ; Mueller, D. ; Hall, D. ; Samotyj, M. ; Randolph, J.
Author_Institution
Electrotek Concepts Inc., Knoxville, TN, USA
Volume
9
Issue
2
fYear
1994
fDate
4/1/1994 12:00:00 AM
Firstpage
1098
Lastpage
1107
Abstract
This paper analyzes an unusual flicker-like disturbance during the operation of a DC arc furnace. A harmonic resonance, excited by an excessive amount of uncharacteristic converter current harmonics, was the main cause of the disturbance. A study was performed in which the phenomenon was duplicated with the Electro-Magnetic Transients Program. The simulation model and results are described. The generation of uncharacteristic converter current harmonics under normal and abnormal converter operation are demonstrated. The significant conditions leading to the unusual 187 Hz disturbance and flicker complaints are discussed
Keywords
arc furnaces; digital simulation; power convertors; power engineering computing; power system harmonics; 187 Hz; 187 Hz voltage distortion; DC arc furnace operation; Electro-Magnetic Transients Program; converter current harmonics; harmonic resonance; power quality; simulation model; voltage flicker; Frequency; Furnaces; Harmonic filters; IEEE members; Power harmonic filters; Power quality; Power system harmonics; Resonance; Steel; Voltage fluctuations;