Title :
A Direct Three-Phase Circuit Analysis-Based Fault Location for Line-to-Line Fault
Author :
Choi, Myeon-Song ; Lee, Seung-Jae ; Lim, Seong-Il ; Lee, Duck-Su ; Yang, Xia
Author_Institution :
Myongji Univ., Yongin
Volume :
22
Issue :
4
fYear :
2007
Firstpage :
2541
Lastpage :
2547
Abstract :
From a direct three-phase circuit analysis, an accurate fault-location algorithm has been obtained for the line-to-line fault as an extension of the author´s previous work for line-to-ground fault location. Robustness of the proposed algorithm to load impedance uncertainty is enhanced by the introduction of impedance compensation using voltage and current measurements. Simulation results show a high degree of accuracy and robustness to load uncertainty.
Keywords :
fault location; load distribution; power distribution faults; power system measurement; current measurement; direct three-phase circuit analysis; distribution feeders; fault location algorithm; impedance compensation; line-to-ground fault location; line-to-line faults; load impedance uncertainty; voltage measurement; Circuit analysis; Circuit faults; Current measurement; Fault location; Impedance measurement; Power system simulation; Robustness; Uncertainty; Voltage; Wavelet packets; Distribution automation; fault location; protective relaying; short-circuit analysis;