Title :
New approach to distance protection for resistive double-phase to earth faults using adaptive techniques
Author :
Moore, P.J. ; Aggarwal, R.K. ; Jiang, H. ; Johns, A.T.
Author_Institution :
Sch. of Electron. & Electr. Eng., Bath Univ., UK
fDate :
7/1/1994 12:00:00 AM
Abstract :
Distance protection is prone to mal-operation under resistive double-phase to earth fault conditions. This is caused by the relay measuring the incorrect impedance to the fault due to the influence of infeed from the remote end of the line. The paper describes two adaptation techniques, one for use with the earth elements, and one for use with the phase elements, which enable the correct impedance to be measured, and hence improve distance protection performance under such fault conditions
Keywords :
electric impedance measurement; electrical faults; power system protection; relay protection; adaptive techniques; distance protection; impedance measurement; relay; resistive double-phase to earth faults;
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
DOI :
10.1049/ip-gtd:19941252