DocumentCode
1118859
Title
Frequency Characteristics Measurement of Overhead High-Voltage Power-Line in Low Radio-Frequency Range
Author
Zajc, M. ; Suljanovic, Nermin ; Mujcic, Aljo ; Tasic, Jurij F.
Author_Institution
Univ. of Ljubljana, Ljubljana
Volume
22
Issue
4
fYear
2007
Firstpage
2142
Lastpage
2149
Abstract
This paper presents measurement results of frequency characteristics of the high-voltage power line in low radio-frequency range: amplitude and phase characteristic, group delay, and input impedance. Measurement results for the 400-kV overhead power-line under operation are presented together with the developed measurement methodology. The methodology provides a method to measure amplitude and phase characteristics, group delay and the return loss of the HV power line for a geographically distributed system utilizing an optical link as a return path. The measurement results confirm very low attenuation with a linear phase, but with oscillations present in all characteristics caused by reflection of the signal on the power line. The complete knowledge of frequency characteristics of the HV power line and noise description is crucial for the design of digital power-line carrier (PLC) systems.
Keywords
carrier transmission on power lines; power overhead lines; digital power-line carrier systems; frequency characteristics measurement; geographically distributed system; group delay; low radio-frequency range; optical link; overhead high-voltage power-line; return loss; Attenuation measurement; Delay; Frequency measurement; Impedance measurement; Loss measurement; Optical fiber communication; Optical losses; Phase measurement; Power measurement; Radio frequency; Digital communications; high-voltage power line; power-line communications; transfer function measurement;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2007.905369
Filename
4302564