• DocumentCode
    1121163
  • Title

    Dielectric Withstand Voltage Tests and Test Conversion Factors for Oil-Filled Transformers

  • Author

    Okabe, Shigemitsu

  • Author_Institution
    High Voltage & Insulation Group Tokyo Electr. Power Co., Yokohama
  • Volume
    15
  • Issue
    2
  • fYear
    2008
  • fDate
    4/1/2008 12:00:00 AM
  • Firstpage
    583
  • Lastpage
    590
  • Abstract
    Dielectric withstand voltage tests to verify oil-filled transformer insulation performance are in most cases carried out using two to three types of tests from lightning impulse (LI), switching impulse (SI) and power frequency (PF) withstand voltage tests based on economical factors and past achievements. Test conversion factors (TCF) are used to evaluate whether the tests cover overvoltages not directly dealt with in tests and the omitted tests. In this paper, insulation characteristics for LI, SI, and PF (AC) are first organized including the recent ones. Several sets of TCF are next calculated based on these characteristics, compared with TCF in present standards, and representative values are then derived. Finally, the dielectric withstand voltage tests specified in present standards are compared using the representative TCF, and the AC withstand voltage test was found to be the severest test overall.
  • Keywords
    impulse testing; insulation testing; power transformer insulation; power transformer testing; transformer oil; dielectric withstand voltage test; lightning impulse voltage; oil-filled transformer insulation; switching impulse voltage; test conversion factors; Dielectrics and electrical insulation; Frequency; Impulse testing; Insulation testing; Lightning; Oil insulation; Power generation economics; Power transformer insulation; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2008.4483480
  • Filename