DocumentCode :
112133
Title :
Thermodynamic Estimation of Transformer Fault Severity
Author :
Jakob, Fredi ; Dukarm, James J.
Author_Institution :
Chem., California State Univ., Sacramento, CA, USA
Volume :
30
Issue :
4
fYear :
2015
fDate :
Aug. 2015
Firstpage :
1941
Lastpage :
1948
Abstract :
Conventional practice for transformer dissolved gas analysis (DGA) is to use concentrations of several fault gases, with or without total dissolved combustible gas, for evaluating apparent fault severity. We suggest a simpler approach based on the normalized energy intensity (NEI), a quantity related directly to fault energy dissipated within the transformer. DGA fault severity scoring based on NEI is shown to be sensitive to all IEC fault types and to be more responsive to shifts in the relative concentrations of the fault gases than scoring based on fault gas concentrations. Instead of eight or more gas concentration limits, NEI scoring requires only two or three limits that can be empirically derived to suit local requirements for any population of mineral-oil-filled power transformers.
Keywords :
fault diagnosis; power transformer insulation; transformer oil; IEC standard; fault energy dissipation; fault gas; fault severity scoring; mineral-oil filled power transformer; normalized energy intensity; thermodynamic estimation; total dissolved combustible gas; transformer dissolved gas analysis; transformer fault severity; Circuit faults; Databases; Hydrogen; Oil insulation; Power transformer insulation; Dissolved gas analysis (DGA); enthalpy; fault energy; fault severity; normalized energy intensity (NEI); transformer;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2015.2415767
Filename :
7065295
Link To Document :
بازگشت