DocumentCode :
1122813
Title :
New Method of Live Line Measuring the Inductance Parameters of Transmission Lines Based on GPS Technology
Author :
Hu, Zhijian ; Chen, Yunping
Author_Institution :
Sch. of Electr. Eng., Wuhan Univ., Wuhan
Volume :
23
Issue :
3
fYear :
2008
fDate :
7/1/2008 12:00:00 AM
Firstpage :
1288
Lastpage :
1295
Abstract :
Based on global positioning system (GPS) technology and differential equation algorithms, a new approach to live line measuring of the inductance parameters of transmission lines with mutual inductance is proposed. The principles and mathematical model of the new method are explained in detail. Data processing by least square algorithm is introduced. To take into account the influence of distributed capacitance of transmission lines, a modified mathematical model is introduced. The hardware structure of the measuring system is given and real-time digital simulator (RTDS) experimental results validate the accuracy of the test system. Finally, an example of live line measuring two 220-kV transmission lines with mutual inductances is given. A comparison of measurement results between the differential equation method and the conventional method is also shown.
Keywords :
Global Positioning System; differential equations; inductance measurement; least squares approximations; power transmission lines; GPS technology; RTDS; data processing; differential equation algorithm; distributed capacitance; global positioning system; inductance parameter measurement; least square algorithm; real-time digital simulator; transmission line; voltage 220 kV; Differential equation algorithm; GPS; RTDS; least-square estimation; live line measurement; mutual inductance; phase-modal transformation; transmission lines; zero-sequence impedances;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2007.916235