Title :
Fault location on a transmission line using synchronized Voltage measurements
Author :
Brahma, Sukumar M. ; Girgis, Adly A.
Author_Institution :
with the Electr. & Comput. Eng. Dept., Clemson Univ., SC, USA
Abstract :
Many methods for fault location using synchronized phasor measurement have been reported in literature. Most of these methods use voltage and current measurements at one or both ends of a transmission line. Accuracy of current measurement is limited by the accuracy of the current transformers (CT) used. This paper describes a fault-location method for transmission lines using only synchronized voltage measurements at both ends of the line, eliminating the inherent error due to CT. The method can be applied to transposed and untransposed lines. The method is tested using results from a steady state fault-analysis program and EMTP.
Keywords :
EMTP; fault location; impedance matrix; phase measurement; power transmission faults; power transmission lines; voltage measurement; EMTP; current measurement; current transformer; fault location; steady state fault-analysis program; synchronized phasor measurement; synchronized voltage measurement; transmission line; Current transformers; Distributed parameter circuits; EMTP; Fault location; Frequency synchronization; Power transmission lines; Protection; Transmission line matrix methods; Transmission line measurements; Voltage measurement; Bus impedance matrix; EMTP; fault-analysis fault location; synchronized phasor measurement;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2003.822532