• DocumentCode
    1123363
  • Title

    Seismic behavior of flexible conductors connecting substation equipment-part I: static and dynamic properties of individual components

  • Author

    Bhuyan, Gouri S. ; Zhai, Endi ; Ghalibafian, Houman ; Ventura, Carlos ; Borthwick, Doug ; Stewart, R.P. ; Rainer, J. Hans

  • Volume
    19
  • Issue
    4
  • fYear
    2004
  • Firstpage
    1673
  • Lastpage
    1679
  • Abstract
    Prompted by recent failures in earthquakes of interconnected high-voltage electrical equipment in substations and a lack of available design information, BC Hydro initiated an experimental program to address this issue. Powertech Labs, in collaboration with BC Hydro and the University of British Columbia (UBC), formulated a research plan to investigate how flexible conductors affect the seismic response of interconnected substation equipment. This paper describes the result of static tests on flexible conductors and of calculations of dynamic properties of equipment in BC Hydro substations. For a set of six interconnected configurations the natural frequencies were calculated and where possible, calibrated to the measured natural frequencies of the equipment.
  • Keywords
    conductors (electric); earthquakes; finite element analysis; substations; BC Hydro; Powertech Labs; University of British Columbia; flexible conductors; interconnected high-voltage electrical equipment; seismic behavior; substation equipment dynamic properties; Circuit breakers; Conductors; Earthquakes; Integrated circuit interconnections; Joining processes; Load flow; Load flow analysis; Seismic measurements; Substations; Testing; Dynamic finite-element analysis; field measurement of dynamic properties; flexible stranded conductors; seismic performance; substation equipment;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.832391
  • Filename
    1339331