DocumentCode :
1123363
Title :
Seismic behavior of flexible conductors connecting substation equipment-part I: static and dynamic properties of individual components
Author :
Bhuyan, Gouri S. ; Zhai, Endi ; Ghalibafian, Houman ; Ventura, Carlos ; Borthwick, Doug ; Stewart, R.P. ; Rainer, J. Hans
Volume :
19
Issue :
4
fYear :
2004
Firstpage :
1673
Lastpage :
1679
Abstract :
Prompted by recent failures in earthquakes of interconnected high-voltage electrical equipment in substations and a lack of available design information, BC Hydro initiated an experimental program to address this issue. Powertech Labs, in collaboration with BC Hydro and the University of British Columbia (UBC), formulated a research plan to investigate how flexible conductors affect the seismic response of interconnected substation equipment. This paper describes the result of static tests on flexible conductors and of calculations of dynamic properties of equipment in BC Hydro substations. For a set of six interconnected configurations the natural frequencies were calculated and where possible, calibrated to the measured natural frequencies of the equipment.
Keywords :
conductors (electric); earthquakes; finite element analysis; substations; BC Hydro; Powertech Labs; University of British Columbia; flexible conductors; interconnected high-voltage electrical equipment; seismic behavior; substation equipment dynamic properties; Circuit breakers; Conductors; Earthquakes; Integrated circuit interconnections; Joining processes; Load flow; Load flow analysis; Seismic measurements; Substations; Testing; Dynamic finite-element analysis; field measurement of dynamic properties; flexible stranded conductors; seismic performance; substation equipment;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.832391
Filename :
1339331
Link To Document :
بازگشت