DocumentCode
1123442
Title
A wavelet multiresolution-based analysis for location of the point of strike of a lightning overvoltage on a transmission line
Author
Chanda, Dipankar ; Kishore, N.K. ; Sinha, Avinash K.
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol., Kharagpur, India
Volume
19
Issue
4
fYear
2004
Firstpage
1727
Lastpage
1733
Abstract
Lightning flashes on extremely high voltage lines are quite common and can lead to insulation breakdown or other line hardware failure causing disruption in supply. An accurate location of the site of failure will result in faster maintenance and restoration of supply. In this paper, a novel technique based on the wavelet multiresolution analysis (MRA) for locating the point of strike of a lightning overvoltage on a transmission line is presented. Lightning strikes at different points on a 400-kV transmission line of different line lengths are simulated by shifting the point of strike of the lightning impulse every 5 km. The Electromagnetic Transient Program (EMTP) [Microtran] is employed to generate the time-domain input signal. Daubechies eight (D8) Wavelet transform is used to analyze lightning overvoltages. The tenth level output of MRA detail signals extracted from the original signals is used as the criterion for the analysis. Extensive simulation work has been done and results indicate that the proposed scheme is very effective in locating the point of strike with reasonable accuracy.
Keywords
EMTP; electric breakdown; fault location; lightning; overvoltage; power transmission lines; wavelet transforms; EMTP; electromagnetic transient program; extremely high voltage lines; failure location; insulation breakdown; lightning flashes; lightning overvoltage strike point location; line hardware failure; supply disruption; time-domain input signal; transmission line; wavelet multiresolution-based analysis; wavelet transform; Breakdown voltage; EMTP; Hardware; Insulation; Lightning; Multiresolution analysis; Signal resolution; Transmission lines; Voltage control; Wavelet analysis; EMTP; MRA; lightning overvoltage; location; multiresolution analysis; wavelet transform;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2004.835382
Filename
1339339
Link To Document