DocumentCode :
1123694
Title :
Hybrid HVDC system for power transmission to island networks
Author :
Andersen, Bjarne R. ; Xu, Lie
Author_Institution :
Power Electron. Activities, Alstom T&D Ltd., Stafford, UK
Volume :
19
Issue :
4
fYear :
2004
Firstpage :
1884
Lastpage :
1890
Abstract :
A hybrid system, comprising a line commutated thyristor high-voltage direct current (HVdc) converter and a static VAR compensator, is proposed in this paper for the connection of networks with no synchronous generation to a main grid. The proposed system combines the robust performance and low capital cost and power loss of a line-commutated HVdc converter, with the fast dynamic performance of a voltage-source-converter (VSC)-based transmission system. The paper describes the principles and control strategies of the proposed system. PSCAD/EMTDC simulations are presented to demonstrate the robust performance and to validate the proposed system during various operating conditions such as black-start, variations of load or generation, and ac fault conditions.
Keywords :
HVDC power convertors; HVDC power transmission; power system simulation; power transmission control; static VAr compensators; HVDC transmission; PSCAD simulations; ac fault conditions; capital cost; control design; high-voltage direct current converter; hybrid HVDC converter; island networks; line commutated thyristor; power loss; power transmission; static VAR compensator; transmission systems; voltage-source-converter; DC generators; HVDC transmission; Hybrid power systems; Mesh generation; Performance loss; Power transmission; Robustness; Static VAr compensators; Synchronous generators; Thyristors; Control design; HVdc transmission; STATCOM; converter; static VAR compensator;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2004.835031
Filename :
1339360
Link To Document :
بازگشت