Scaled low-voltage side surge current tests on a model distribution system
Author :
McMillen, C.J. ; Caverly, D.W. ; Schoendube, C.W.
Author_Institution :
General Electric Co., Hickory, NC, USA
Volume :
3
Issue :
2
fYear :
1988
fDate :
4/1/1988 12:00:00 AM
Firstpage :
655
Lastpage :
661
Abstract :
The model system and the test procedures are described. The tests revealed the most significant circuit parameters affecting the magnitude and distribution of currents that will flow in a customer´s wiring. The tests also showed that distribution transformers utilizing interlaced windings rated 240/120 volts are unlikely to increase significantly the magnitude of surges in comparison to noninterlaced windings of the same rating
Keywords :
power transformers; surges; transformer testing; transformer windings; 120 V; 240 V; distribution transformers; interlaced windings; scaled LV side surge current tests; Circuit simulation; Circuit testing; Joining processes; Lightning; Performance evaluation; Resistors; Surges; System testing; Transformers; Wiring;