DocumentCode
1126482
Title
Direct control algorithm for doubly fed induction generators in weak grids
Author
Wong, K.C. ; Ho, S.L. ; Cheng, K.W.E.
Author_Institution
Dept. of Electr. Eng., Hong Kong Polytech. Univ., Kowloon
Volume
3
Issue
4
fYear
2009
fDate
7/1/2009 12:00:00 AM
Firstpage
371
Lastpage
380
Abstract
An algorithm utilising direct feedbacks of torque and reactive power for the control of a doubly fed induction generator (DFIG) is proposed. Although the algorithm is based on field-oriented control, the algorithm calculates the feedback and feed-forward variables in the stator reference frame to reduce the number of coordinate transformations. Since the algorithm uses a single-loop approach instead of a cascaded loop design, the tuning of the controller is easier and the response time is faster when compared to those of most existing methods. The internal model control (IMC) design method is used in the proposed scheme to formulate the controller parameters. Measures on the possible voltage variations are included to increase the robustness of the system. Computer simulation and experimental implementation are reported. The results show that the algorithm can control the torque and reactive power independently. Harmonic distortions generated by the system are not noticeable because of the use of constant switching frequency.
Keywords
asynchronous generators; control system synthesis; feedback; harmonic distortion; machine vector control; power grids; reactive power control; torque control; IMC design method; doubly fed induction generator control; field-oriented control; harmonic distortion; internal model controller; power grid; reactive power control; single-loop approach; stator reference frame; torque control;
fLanguage
English
Journal_Title
Electric Power Applications, IET
Publisher
iet
ISSN
1751-8660
Type
jour
DOI
10.1049/iet-epa.2008.0039
Filename
5154118
Link To Document