DocumentCode
1127917
Title
Track it or crack it
Author
Lebenhaft, Ed
Author_Institution
Schweitzer Eng. Labs. Inc., Pullman
Volume
14
Issue
2
fYear
2008
Firstpage
58
Lastpage
61
Abstract
The article demonstrates that the first-order thermal model is superior in protecting motors with cyclic loads. The first-order thermal model faithfully tracks cyclic load without a premature process interruption due to motor trip, even though the maximum current exceeds the service factor (SF) rating, as long as the motor per unit (p.u.) temperature stays below the design limit of SF. As the period of the cyclic current approaches the motor RTC and the maximum current exceeds the SF rating, the motor temperature will approach the motor design limit p.u. temperature and will result in a motor trip and process interruption. It is imperative when applying a motor to a cyclic-load application that the thermal and electrical characteristics of the motor be scrutinized and compared with the mechanical process characteristics to ensure compatibility.
Keywords
motor protection; cyclic loads; first-order thermal model; motor per unit temperature; motor protection; service factor; AC motors; Bars; Capacitance; Heat transfer; Magnetic fields; Protection; Rotors; Stators; Thermal loading; Thermal resistance;
fLanguage
English
Journal_Title
Industry Applications Magazine, IEEE
Publisher
ieee
ISSN
1077-2618
Type
jour
DOI
10.1109/MIA.2007.914277
Filename
4487125
Link To Document