Validation of Voltage Sag Simulation Tools: ATP and Short-Circuit Calculation Versus Field Measurements
Author :
Filho, Jose Maria Carvalho ; Leborgne, Roberto Chouhy ; De Abreu, José Policarpo G ; Novaes, Eder G C ; Bollen, Math H J
Author_Institution :
Itajuba Fed. Univ., Itajuba
Volume :
23
Issue :
3
fYear :
2008
fDate :
7/1/2008 12:00:00 AM
Firstpage :
1472
Lastpage :
1480
Abstract :
Two methods to calculate voltage sags are validated against actual measurements. One of the methods is a short-circuit calculation program resulting directly in sag magnitude during the fault. The other is an electromagnetic transient program resulting in voltage waveform as a function of time. Individual sag characteristics and system performance obtained by deterministic simulation and measurement are compared. The influence of the random variables (prefault voltage, fault location and fault impedance) is investigated.
Keywords :
electromagnetic fields; fault location; power supply quality; power system simulation; transient analysis; alternative transients program; electromagnetic transient program; fault impedance; fault location; field measurements; short-circuit calculation; voltage sag simulation tools; voltage waveform; Measurement; power quality (PQ); simulation; voltage sag (dip);