    Non-Contact Measurement of Current Distribution in Parallel Conductors by Using Hall Sensors

  • Author

    Park, Myungjin ; Byun, Sangbeom ; Kim, Wooseok ; Lee, Jikwang ; Choi, Kyeongdal ; Lee, Haigun

  • Author_Institution
    Korea Electr. Eng. & Sci. Res. Inst., Seoul
  • Volume
    18
  • Issue
    2
  • fYear
    2008
  • fDate
    6/1/2008 12:00:00 AM
  • Firstpage
    1135
  • Lastpage
    1138
  • Abstract
    A parallel HTS conductor to flow large current is essential for applications of HTS power device. Non-uniform current distribution in the parallel conductor is caused mainly due to the difference of inductance. There are a contact method which measures current directly and a non-contact method which measure indirectly. But current distribution of each conductor in parallel conductors can not be measured with conventional method. In this paper, we researched a measurement method to identify current distribution of the parallel conductor indirectly with Hall sensors and compared with the analysis results by 2-D FEM.
  • Keywords
    Hall effect transducers; current distribution; electric current measurement; finite element analysis; high-temperature superconductors; 2D FEM; HTS power device; hall sensors; high-temperature superconductors; noncontact measurement; nonuniform current distribution; parallel conductors; Current distribution; HTS; Hall sensor;
  • fLanguage
    English
  • Journal_Title
    Applied Superconductivity, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1051-8223
  • Type

    jour

  • DOI
    10.1109/TASC.2008.922512
  • Filename
    4494477