• DocumentCode
    1145527
  • Title

    Loss measurement in high voltage thyristor valves

  • Author

    Cepek, Milan ; Douville, Jean ; Fecteau, Gilles ; Malewski, Ryszard

  • Author_Institution
    Hydro-Quebec Res. Inst., Montreal, Que., Canada
  • Volume
    9
  • Issue
    3
  • fYear
    1994
  • fDate
    7/1/1994 12:00:00 AM
  • Firstpage
    1222
  • Lastpage
    1236
  • Abstract
    No measuring method is presently available for direct and sufficiently accurate evaluation of power losses in thyristor valves used in HVDC converter substations and static VAr controllers. This paper presents a measuring method to be be used during the valve type tests with the intention to verify the guaranteed loss characteristic. The method was validated under laboratory conditions by comparison to a sophisticated calorimetric technique. An uncertainty of 1% was achieved at conditions simulating full load operation. Voltage across and current through the valve are recorded in discrete steps and digitized. The loss is then calculated as their product. Special current and voltage sensors were developed to cover a very high dynamic range of the measured quantities. A high resolution, multichannel digital recorder was used for simultaneous registration of two voltage and two current signals. The method is of a general application, since the valve is treated as a two port circuit. Therefore, it can be used to measure loss in other nonlinear components and apparatus, where large dynamic changes of the measured quantities preclude application of conventional techniques
  • Keywords
    DC power transmission; loss measurement; losses; power convertors; semiconductor device testing; static VAr compensators; substations; thyristor applications; HVDC converter substations; current and voltage sensors; high voltage thyristor valves; loss characteristic; power losses; static VAr controllers; two port circuit; uncertainty; voltage sensors; HVDC transmission; Loss measurement; Power measurement; Reactive power; Static power converters; Substations; Testing; Thyristors; Valves; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.311148
  • Filename
    311148