DocumentCode
1146267
Title
Relation of Transformer Design to Fire Protection [includes discussion]
Author
Treanor, E.D. ; Whitman, L.C.
Author_Institution
FELLOW AIEE, General Electric Company, Pittsfield, Mass.
Volume
71
Issue
1
fYear
1952
Abstract
This contribution to the discussion of the fire risks of transformers is limited to tests on the materials which enter the apparatus and their probable behavior. Comparisons are made regarding flammability of the solid insulations, as well as the gases evolved from them. These gases are analyzed for chemical composition and volume, and calculations made regarding their probable action in a transformer. The flammability characteristics of the various classes are shown to overlap to a considerable degree, especially for the insulation classes B and H. This emphasizes the fact that insulation classes are intended to define temperature limitations as regards aging, but do not necessarily classify flammability.
Keywords
Chemical analysis; Fires; Flammability; Gas insulation; Gases; Materials testing; Power transformer insulation; Protection; Solids; Temperature;
fLanguage
English
Journal_Title
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher
ieee
ISSN
0097-2460
Type
jour
DOI
10.1109/AIEEPAS.1952.4498527
Filename
4498527