Title :
A New Approach to E.H.V. Direction Comparisn Protection Using Digital Signal Processing Techniqles
Author :
Johns, A.T. ; Martin, M.A. ; Barker, A. ; Walker, E.P. ; Crossley, P.A.
Author_Institution :
University of Bath, Claverton Down, Bath, United Kingdom
fDate :
4/1/1986 12:00:00 AM
Abstract :
Some problems concerning the performance of superimposed component directional relays are discussed, and it is shown that the basic directional criteria can be violated due to travelling wave phenomena or for fault occurrence approaching a voltage zero. A relay design is developed using digital signal processing techniques to overcome these problems. Tlhe complete relay is tested using a typical 40OkV transmission line application.
Keywords :
Digital relays; Digital signal processing; Performance evaluation; Power system protection; Power system relaying; Power system reliability; Power transmission lines; Protective relaying; System testing; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.1986.4307930