Field Measurement of Ground Fault Current Distribution and Substation Ground Impedance at LG-2, Québec
Author
Fortin, J. ; Sarmiento, H.G. ; Mukhedkar, D.
Author_Institution
Essais de réseau et Analyse Hydro-Québec Montréal, Canada
Volume
1
Issue
3
fYear
1986
fDate
7/1/1986 12:00:00 AM
Firstpage
48
Lastpage
60
Abstract
Field measurements of ground fault current distribution and substation ground impedance of the LG-2 complex in Quebec, are presented. A high current measuring technique is described in Appendix A, Appendix B illustrates the way current distribution and efficiency were determined. The effectiveness of each grounding element is calculated, showing that the grounding conductors and not the ground grid drain most of the fault current.
Keywords
Conductors; Current distribution; Current measurement; Electrodes; Fault currents; Grounding; Impedance measurement; Power measurement; Substations; Wires;