Abstract :
A new insulation diagnostic method for XLPE cables containing water trees is presented. A dc component in the ac charging current of these cables was found to be a significant sign of the existence of water trees. The dc component has good correlations with such insulation characteristics of aged XLPE cables as ac breakdown voltage and dc leakage current. Criteria for insulation diagnosis of 6.6kV XLPE cables have been established. An automatic insulation diagnostic device has been developed. It is now being applied to hot-line XLPF cables in distribution systems of TEPCO (The Tokyo Electric Power Co., Inc.).