DocumentCode :
1148183
Title :
Characteristics of Short Circuit Electromagnetic Forces in Three Phase Enclosure Type Gas Insulated Bus
Author :
Hama, H. ; Marutani, T. ; Takatsuka, K. ; Nitta, T. ; Tanabe, T.
Author_Institution :
Mitsubishi Electric Corporation, Amagasaki, Japan
Volume :
2
Issue :
2
fYear :
1987
fDate :
4/1/1987 12:00:00 AM
Firstpage :
367
Lastpage :
373
Abstract :
The effects of the enclosure material to the electromagnetic force and the dynamic performances of the force have been measured in case of 3¿ fault and ¿-¿ fault, using three phase enclosure type gas insulated bus (GIB) models. The analysis for the electromagnetic force has been performed and compared with the experimental results. Mild steel and stainless steel enclosure have little influence to the electromagnetic forces between the phase conductors, whereas the forces are fully reduced by the existence of aluminum alloy enclosure.
Keywords :
Circuit faults; Electromagnetic analysis; Electromagnetic forces; Electromagnetic measurements; Electromagnetic modeling; Force measurement; Gas insulation; Performance evaluation; Phase measurement; Steel;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1987.4308117
Filename :
4308117
Link To Document :