DocumentCode :
1148310
Title :
Service Restoration Following a Major Failure on the Hydro-Québec Power System
Author :
Morin, Gaston
Author_Institution :
Hydro-Québec Montreal, Canada
Volume :
2
Issue :
2
fYear :
1987
fDate :
4/1/1987 12:00:00 AM
Firstpage :
454
Lastpage :
463
Abstract :
Service restoration following a major power failure can occasion voltage problems on weak EHV systems from the point of view of both steady-state and temporary operation. This is due to the use of long EHV transmission links between the production sites and the load centres, which can cause large amounts of reactive power to be generated, and low short-circuit level, leading to low-frequency resonance, further excited by the presence of transformers. This paper describes an approach to service restoration which should speed up the process of restoring service to customers while at the same time limiting the risks of damage to equipment.
Keywords :
Power generation; Power system harmonics; Power system restoration; Production; Reactive power; Resonance; Steady-state; Surges; Transformers; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1987.4308129
Filename :
4308129
Link To Document :
بازگشت