Title
Electrical strength of paper-oil insulation subjected to composite voltages
Author
Mosinski, Franciszek ; Wodzinski, Jerzy ; Sikorski, Lukasz ; Ziencikiewicz, Jozef
Author_Institution
High Voltage Dept., Lodz Tech. Univ., Poland
Volume
1
Issue
4
fYear
1994
fDate
8/1/1994 12:00:00 AM
Firstpage
615
Lastpage
623
Abstract
The results of a composite voltage, ac with lightning impulse (LI) tests of a paper-oil insulation model are presented. It was demonstrated that the presence of the background ac voltage leads to a decrease in LI breakdown voltage. This is particularly conspicuous at opposite polarities. The dispersion of LI breakdown voltages decreases save for the case when the LI is superimposed on the opposite polarities. The dispersion of LI breakdown voltages decreases save for the case, when the LI is superimposed on the opposite polarity peak value of the ac sinusoid. In this critical case the combined breakdown voltage (ac+LI) may be even lower than the ac one
Keywords
electric strength; impulse testing; insulating oils; insulation testing; life testing; paper; background ac voltage; breakdown voltages; composite voltages; electrical strength; lightning impulse; opposite polarity peak value; paper-oil insulation; Circuit testing; Control systems; Dielectrics and electrical insulation; Impulse testing; Insulation testing; Lightning; Oscilloscopes; Power transformer insulation; System testing; Voltage;