DocumentCode
1148591
Title
Factors Affecting Loadbreak Elbow Connector Switching Speeds
Author
Filter, R. ; Jones, A.S.
Author_Institution
Ontario Hydro Research Division Toronto, Ontario
Volume
2
Issue
3
fYear
1987
fDate
7/1/1987 12:00:00 AM
Firstpage
645
Lastpage
650
Abstract
A test program to assess the factors affecting loadbreak elbow switching speeds was initiated after several field failures suggested that inadequate switching speeds are increasingly common, especially with higher voltage elbows. It was found that tool type greatly affects switching speeds, that loadbreak elbow condition affects the range of speeds attained with any tool, and that lineman chacteristics only minimally influence speeds. To date, none of the above factors are included in the ANSI/IEEE-386 test Standard. The results of these tests underscore the importance of incorporating additional parameters into switching test clauses in future revisions of the Standard.
Keywords
ANSI standards; Connectors; Contacts; Elbow; Filters; Manufacturing; Power transformer insulation; Switches; System testing; Voltage;