Title :
Series Capacitor SF-6 Bypass Interrupter
Author :
Prange, Thomas W. ; Soule, Gailen B.
Author_Institution :
Idaho Power Company Boise, Idaho
fDate :
7/1/1987 12:00:00 AM
Abstract :
Series capacitor banks on transmission lines ave two types of bypass switches; high-speed switches located on the insulated capacitor platforms for operation, and manually-operated line switches to isolate the bank for maintenance. Air break switches used for maintenance bypass on 345 kV series capacitors could not successfully transfer line current without heavy arcing. An SF-6 interrupter like that manufactured for transformer protection, was selected for a simple retrofit replacement.
Keywords :
Capacitors; Interrupters; Manufacturing; Personnel; Power generation; Power system protection; Power transformer insulation; Power transmission lines; Substations; Switches;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.1987.4308171