Title : 
An efficient method for calculation of electric field in three-core power cables
         
        
            Author : 
Delgado León, Miguel Z. ; Murari, Carlos A F
         
        
            Author_Institution : 
DSEE-FEE-UNICAMP, Campinas, Brazil
         
        
        
        
        
            fDate : 
7/1/1996 12:00:00 AM
         
        
        
        
            Abstract : 
In this paper we applied the superposition principle with a new basic conductor voltage condition for the computed electric field in three-core cables and the results obtained have higher accuracy and lower computational time than the previous works. The maximum potential error is not more than 0.050% and the maximum field deviation angle is not more than 0.011°. The electric field problem under arbitrary conductor voltage condition is reduced to a field computation for a new basic conductor voltage condition (0,1,-1) which reduces the computing time because it doesn´t require the repetitive solution of the algorithm for different ωt values. With this new configuration, it is possible to take advantages of a symmetrical conductor arrangement reducing the number of charges necessary for the field calculation and the superposition principle is applied only two times
         
        
            Keywords : 
conductors (electric); electric fields; power cables; compressed gas insulated cables; conductor voltage condition; electric field calculation; electric potential; maximum field deviation angle; maximum potential error; superposition principle; symmetrical conductor arrangement; three core belted cables; three-core power cables; Cable insulation; Computational modeling; Conductors; Design optimization; Gas insulation; Power & Energy Society; Power cables; Quantum computing; Stress; Voltage;
         
        
        
            Journal_Title : 
Power Delivery, IEEE Transactions on