DocumentCode
1150478
Title
Validation of phasor calculations in the macrodyne PMU for California-Oregon Transmission Project tests of March 1993
Author
Hauer, J.F.
Author_Institution
Pacific Northwest Lab., Richland, WA, USA
Volume
11
Issue
3
fYear
1996
fDate
7/1/1996 12:00:00 AM
Firstpage
1224
Lastpage
1231
Abstract
Faults applied during the March 1993 commissioning tests for the California-Oregon Transmission Project produced 14 Hz transient oscillations that were conspicuous in BPB´s enhanced transducers at Malin, and in PG&E´s Dynamic System Monitor at Table Mountain. Prony analysis of high speed fault data provided a detailed model for the underlying network resonance signal, and a basis for validating transient performance of a macrodyne phasor measurement unit (PMU) at the test site. This instrument, which is closely associated with EPRI´s FACTS project, provides useful insight into emerging technology for high speed digital transducers. The phasor calculations are found to be of very high quality, but filtering enhancements are recommended for broadband applications
Keywords
digital instrumentation; electrical faults; fault diagnosis; power system measurement; power system transients; power transmission lines; resonance; transducers; 14 Hz; BPB enhanced transducers; California-Oregon Transmission Project tests; EPRI FACTS project; Malin; PG&E Dynamic System Monitor; Prony analysis; Table Mountain; broadband applications; faults; filtering enhancements; high speed digital transducers; high speed fault data; macrodyne phasor measurement unit; network resonance signal; phasor calculations; transient performance validation; Filtering; Instruments; Monitoring; Performance analysis; Phasor measurement units; Resonance; Signal analysis; System testing; Transducers; Transient analysis;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.517475
Filename
517475
Link To Document