• DocumentCode
    1150594
  • Title

    Reduction of interference on substation low voltage wiring

  • Author

    Gavazza, R.J. ; Wiggins, C.M.

  • Author_Institution
    Pacific Gas & Electr. Co., San Francisco, CA, USA
  • Volume
    11
  • Issue
    3
  • fYear
    1996
  • fDate
    7/1/1996 12:00:00 AM
  • Firstpage
    1317
  • Lastpage
    1329
  • Abstract
    This paper describes test results and mitigation methods of electromagnetic interference (EMI) on control and low voltage circuits in substations caused by air disconnect switch operation. The tests are focused on a comparison between unshielded and shielded circuits from capacitively coupled voltage transformers (CCVT) and other equipment circuits in the vicinity. New test data are presented comparing unshielded and shielded cables and transient currents on all connections to the CCVT including the pedestal and ground strap. The paper gives a practical and understandable explanation of the causes of EMI in substations and how shielded cable and parallel ground conductors reduce interference. Design guidelines are listed in the conclusion
  • Keywords
    cable sheathing; circuit breakers; electromagnetic interference; instrument transformers; potential transformers; power system measurement; power system transients; substations; wiring; EMI; air disconnect switch operation; capacitively coupled voltage transformers; design guidelines; low voltage wiring; parallel ground conductors; shielded cables; substation; switching transients; transient currents; unshielded cables; Cable shielding; Circuit testing; Coupling circuits; Electromagnetic interference; Low voltage; Substations; Switches; Switching circuits; Voltage control; Wiring;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.517486
  • Filename
    517486