DocumentCode
1150594
Title
Reduction of interference on substation low voltage wiring
Author
Gavazza, R.J. ; Wiggins, C.M.
Author_Institution
Pacific Gas & Electr. Co., San Francisco, CA, USA
Volume
11
Issue
3
fYear
1996
fDate
7/1/1996 12:00:00 AM
Firstpage
1317
Lastpage
1329
Abstract
This paper describes test results and mitigation methods of electromagnetic interference (EMI) on control and low voltage circuits in substations caused by air disconnect switch operation. The tests are focused on a comparison between unshielded and shielded circuits from capacitively coupled voltage transformers (CCVT) and other equipment circuits in the vicinity. New test data are presented comparing unshielded and shielded cables and transient currents on all connections to the CCVT including the pedestal and ground strap. The paper gives a practical and understandable explanation of the causes of EMI in substations and how shielded cable and parallel ground conductors reduce interference. Design guidelines are listed in the conclusion
Keywords
cable sheathing; circuit breakers; electromagnetic interference; instrument transformers; potential transformers; power system measurement; power system transients; substations; wiring; EMI; air disconnect switch operation; capacitively coupled voltage transformers; design guidelines; low voltage wiring; parallel ground conductors; shielded cables; substation; switching transients; transient currents; unshielded cables; Cable shielding; Circuit testing; Coupling circuits; Electromagnetic interference; Low voltage; Substations; Switches; Switching circuits; Voltage control; Wiring;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.517486
Filename
517486
Link To Document