DocumentCode :
1150769
Title :
Calculation of single phase AC and monopolar DC hybrid corona effects
Author :
Zhao, T. ; Sebo, S.A. ; Kasten, D.G.
Author_Institution :
Dept. of Electr. Eng., Ohio State Univ., Columbus, OH, USA
Volume :
11
Issue :
3
fYear :
1996
fDate :
7/1/1996 12:00:00 AM
Firstpage :
1454
Lastpage :
1463
Abstract :
Operating a hybrid HVAC and HVDC power transmission line is an option for increasing the efficiency of power transmission and overcoming the difficulties in obtaining a new right-of-way. This paper proposes a new calculation method for the study of hybrid power line corona. The proposed method can be used to calculate DC corona losses and corona currents in DC or AC conductors for single phase AC and monopolar DC hybrid lines. Profiles of electric field strength and ion current density at ground level can be estimated. The effects of the presence of an energized AC conductor on DC conductor corona and DC voltage on AC conductor corona are included in the method. Full-scale and reduced-scale experiments were utilized to investigate the hybrid line corona effects. Verification of the proposed calculation method is given
Keywords :
HVDC power transmission; corona; current density; electric fields; power system interconnection; power transmission lines; DC corona losses; corona currents; electric field strength; hybrid HVAC/HVDC power transmission line; hybrid corona effects; ion current density; monopolar lines; single-phase lines; Conductors; Corona; Current density; Electric fields; HVDC transmission; Power system modeling; Power system reliability; Power transmission; Student members; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.517504
Filename :
517504
Link To Document :
بازگشت