Title :
Reduction of audible noise using asymmetrical bundles for 1000 kV transmission lines: full-scale test results of Akagi test line
Author :
Tanabe, Kazuo ; Takebe, Toshiro ; Isozaki, Masanori
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
fDate :
7/1/1996 12:00:00 AM
Abstract :
Long-term tests of asymmetrical bundles which have the potential to suppress corona activity on conductor bundles have been carried out in the Akagi test line, and their corona performance, mainly audible noise, was measured. Asymmetrical bundles generally show good performance; however, the “added system”, which is classified as an asymmetrical bundle due to the addition of a subconductor at the bottom of regular symmetrical conductor bundles, shows better performance. These reduction techniques can be applied to actual 1000 kV transmission lines because of their good corona-suppressing performance, if problems such as mechanical performance and unbalanced current passing through individual subconductors can be resolved
Keywords :
acoustic noise; acoustic noise measurement; corona; noise abatement; overhead line conductors; power overhead lines; power transmission lines; random noise; 1000 kV; Akagi test line; asymmetrical bundles; audible noise measurement; audible noise reduction; corona activity suppression; full-scale test results; hum noise; mechanical performance; random noise; regular symmetrical conductor bundles; subconductor; transmission lines; unbalanced current; Acoustic noise; Conductors; Corona; Noise level; Power transmission lines; Spirals; Testing; Transmission lines; Wires; Working environment noise;
Journal_Title :
Power Delivery, IEEE Transactions on