• DocumentCode
    1150800
  • Title

    Reduction of audible noise using asymmetrical bundles for 1000 kV transmission lines: full-scale test results of Akagi test line

  • Author

    Tanabe, Kazuo ; Takebe, Toshiro ; Isozaki, Masanori

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    11
  • Issue
    3
  • fYear
    1996
  • fDate
    7/1/1996 12:00:00 AM
  • Firstpage
    1482
  • Lastpage
    1491
  • Abstract
    Long-term tests of asymmetrical bundles which have the potential to suppress corona activity on conductor bundles have been carried out in the Akagi test line, and their corona performance, mainly audible noise, was measured. Asymmetrical bundles generally show good performance; however, the “added system”, which is classified as an asymmetrical bundle due to the addition of a subconductor at the bottom of regular symmetrical conductor bundles, shows better performance. These reduction techniques can be applied to actual 1000 kV transmission lines because of their good corona-suppressing performance, if problems such as mechanical performance and unbalanced current passing through individual subconductors can be resolved
  • Keywords
    acoustic noise; acoustic noise measurement; corona; noise abatement; overhead line conductors; power overhead lines; power transmission lines; random noise; 1000 kV; Akagi test line; asymmetrical bundles; audible noise measurement; audible noise reduction; corona activity suppression; full-scale test results; hum noise; mechanical performance; random noise; regular symmetrical conductor bundles; subconductor; transmission lines; unbalanced current; Acoustic noise; Conductors; Corona; Noise level; Power transmission lines; Spirals; Testing; Transmission lines; Wires; Working environment noise;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.517507
  • Filename